GE Consumer & IndustrialElectrical DistributionAF-650 GPTM & AF-600 FPTM OPCMBTCP Modbus TCP OptionThe instructions do not purport to cover
3.1.3 LED BehaviourThe option has 3 bi-coloured LEDs according to ODVA specifications:LED Label DescriptionMS Module StatusNS1 Network Status Ethernet
3.1.4 TopologyThe OPCMBTCP features a build-in Ethernet-switch, thus having two Ethernet RJ-45 connectors. This enables the possibility for connecting
NB!Please observe that mounting drives of different power-sizes in a line topology may result in unwanted power-off behaviour.Smaller drives discharge
3.1.6 Recommended Design RulesWhile designing Ethernet networks special attention and caution must be taken regarding active network components.While
3.1.7 EMC PrecautionsThe following EMC precautions are recommended in order to achieve interference-free operation of the Ethernet network. Additional
Modbus TCP144
4 How to Configure4.1.1 IP SettingsAll IP-related parameters are located in parameter group EN-##:EN-00 IP Address AssignmentEN-01 IP AddressEN-02 Sub
Par. EN-03, Default Gateway is optional and only used in routed networks.Par. EN-06, Name ServersPar. EN-07, Domain NamePar. EN-08, Host NameAre used
4.1.3 Configuring the ScannerFor configuring the scanner to communicate to the drive, no system (e.g. EDS, GSD file) file is needed. The AF-600 FP/AF-
After selecting “OK” the network “GE” should show up under Networks and by selecting the Network, the main configuration page will be shown.In this me
Contents1 Safety3Safety Note 3Safety Regulations 3Warning against Unintended Start 42 Introduction5Introduction 5About this Manual 5Assumptions 5Backg
130BB260.10In This menu following settings has to be made:Menu Menu point SettingFunction Function ETH TCP IPNet Link Net Link GEAt this time the “GE”
By first selecting the GE network and secondly selecting the IO Scanning tab, the scanning list appears. You will have to fill out the list as shown h
4.1.4 IP trafficThe use of Ethernet based network for industrial automation purposes, calls for careful and thorough network design. Especially the us
Modbus TCP225
5How to Control5.1.1 How to Control the Frequency ConverterThis section describes codes which can be used in the function and data fields of a Modbus
5.2.4 Holding Register AddressingHolding registersRegister Number Description00001-00006 Reserved00007 Last error code from an Drive data object inte
5.2.5 Parameter HandlingThe PNU (Parameter Number) is translated from the register address contained in the Modbus read or write message. The paramete
5.2.11 Cross Reference ListAll parameters in the AF-650 GP and the AF-600 FP are named with one ortwo letters, a "-" and a number e.g. F-07.
5.2.13 Modbus Exception CodesFor a full explanation of the structure of an exception code response, please refer to the section Modbus RTU Message Fra
5.4 GE Drive Control Profile5.4.1 GE Drive Control Profile → Illustration 5.1
Bus Speed Reference Value 316 Parameters33Parameter Group O-## 33Parameter Group EN-## 37Modbus TCP 40Parameter List 44Data Types 46Data Types Support
Bit 06, Ramp stop/start:Bit 06 = ‘0’ causes a stop, in which the motor speed is deceled to stop via theselected decel parameter. Bit 06 = ‘1’ permits
5.4.2 Status Word according to Drive Profile (STW) → Illustration 5.2: (par. O-10 Contr
5.5 Reference Handling5.5.1 Bus Speed Reference ValueIn Drive-Profile (par. O-10 = [0] Drive profile) the reference is scaled as a normalized relative
Modbus TCP326
6 Parameters6.1 Parameter Group O-##O-01 Control SiteOption: Function:The setting in this parameter overrides the settings in par. O-50 Coasting Sele
O-04 Control Word Timeout FunctionSelect the time-out function. The time-out function activates when the control word fails to be updated within the
O-10 Control Word ProfileSelect the interpretation of the control and status words corresponding to the installed network. Only the selections valid
O-52 DC Brake SelectOption: Function:Select control of the DC brake via the terminals (digital input) and/or via the network.[0] Digit Input Activate
O-55 Set-up SelectOption: Function:Select control of the drive set-up selection via the terminals (digital input) and/or via the network.[0] Digit In
EN-04 DHCP ServerRange: Function: [000.000.000.000 – 255.255.255.255] Read only. Displays the IP address of the found DHCP or BOOTP server.NB!A powe
1 Safety1.1.1 Copyright, Limitation of Liability and Revision RightsThis publication contains information proprietary to GE. By accepting and using th
EN-13 Link SpeedOption: Function:Forces the link speed for each port in 10 or 100 Mbps. If par. EN-12 is set to: ON, this parameter is readonly and d
6.2.1 Modbus TCPEN-40 MODBUS TCP StatusRange: Function:[0][1]Read only. Displays the Modbus TCP- specific 16-bit Status word.Bit Description Bit = [0
EN-82 SMTP ServiceOption: Function:[0] * Disable Disables the SMTP (e-mail) service on the option.[1] Enable Enables the SMTP (e-mail) service on the
EN-94 Broadcast Storm ProtectionOption: Function:The built-in switch is capable of protecting the switch system from receiving too many broadcast pac
EN-99 Media CountersOption: Function:Read only. Advanced Interface counters, from build-in switch, can be used for low-level trouble-shooting,The par
6.3 Parameter ListPar. No. # Parameter description Default value 4-set-up Change during opera-tionConver-sion indexTypeO-0#O-01 Control Site null All
Parameter Number Parameter Description Default Value Range Conversion Index Data Type ArrayEN-0# IP SettingsEN-00 IP Address Assignment 0.0.0.0 0 - 25
6.4 Data Types6.4.1 Data Types Supported by AF-650 GP/AF-600 FPConversion IndexThis number to the left refers to a conversion figure on the right to b
7 Troubleshooting7.1 Troubleshooting7.1.1 Step-by-step TroubleshootingCheck: LEDsThe option contains two LEDs to indicate the state of the device and
7.1.2 Alarm Word and Warning WordAlarm word and warning word are shown in the display in Hex format. If there is more than one warning or alarm, a sum
1.1.4 Warning against Unintended Start1. The motor can be brought to a stop by means of bus commands while the variable speed drive is connected to ma
Bit (Hex) Warning word 2 (Par. DR-93)00000001 Start Delayed00000002 Stop Delayed00000004 Clock Failure00000008 Firemode was active00000010 Reserved000
Bit (Hex) Extended status word 2 (Par. DR-95)AF-600 FP only !!00000001 Off00000002 Hand/Auto00000004 PROFIbus OFF1 active00000008 PROFIbus OFF2 active
IndexAAbbreviations 6Alarm Word 48Assumptions 5BBackground Knowledge 5CCabling 41Cabling 47Coasting Select O-50 35Configurable Control Word Ctw O-14 3
OOverview 7PParameter Values 25Parameters 4, 15, 16Parameters 16Preset Reference Select O-56 37RReference 28, 30Reference 6, 28, 31, 49Reset Control W
GE Consumer & IndustrialElectrical DistributionAF-650 GPTM & AF-600 FPTM OPCMBTCP Modbus TCP OptionThe instructions do not purport to cover
2Introduction2.1 Introduction2.1.1 About this ManualFirst time users can obtain the most essential information for quick installation and set-up in th
2.1.4 Modbus ConformanceThe Modbus option is tested to conform to the Modbus standards, and is certified, towards conformance test level version 3. 2.
3 How to Install3.1.1 The Modbus TCP OptionOPCMBTCPIllustration 3.1: Overview of the optionModbus TCP7 3
3.1.2 How to Install Option in Frequency ConverterItems required for installing a network option in the frequency converter:- The network option- Netw